Many customer wonder why hydrostatic level sensors fail due to lightning strikes, even though they ordered a level sensor with integrated lightning protection. Understanding how the lightning protection works and how lightning strikes affect hydrostatic level sensors is essential in resolving this confusion.
When submersible pressure sensors, a special kind of hydrostatic level sensors, were first installed into reservoirs and lakes to monitor level, the sensor would become burned or destroyed after a lightning storm or inclement weather periods. This prompted much research in to the aftereffect of lightning storms on the instrumentation in reservoirs and the cabling to and from the site.
What lightning protection really means
The first thing to understand is that the result of a lightning strike is considerably different based on how close to the pressure sensor the lightning strikes in to the ground or installation. It is fair to state that no level sensor will survive a direct or very close nearby lightning strike, where often the whole cabin including all installed electronics will undoubtedly be incinerated by direct hits.
However, more distant hits will only raise the Voltage differential by for instance 1500 Volts. In case a local lightning strike raises the electric potential of a reservoir, the level sensor may provide the shortest method for the raised voltage and current to earth. The power will then dissipate into the ground via the particular level probe and therefore destroy or damage its electronics. This may equally be the case when overhead wires take a hit.
How does lightning protection in level sensors work?
However, sensors can be protected from these lightning strikes by installing or integrating a transient voltage protection in to the hydrostatic level sensor. Due to the short nature of the voltage pulse, an element may be suited to or built-into the sensor that acts on rising differences in voltage potential. If the voltage goes above say 50 Volts, this lightning protection can short-circuit the electronic circuit to ground, allowing a path to ground for the surge and protecting the electronics around the maximum specified voltage potential.
The component would normally operate in a non-conductive state, but will be conductive for a voltage transient, allowing the voltage spike to flow harmlessly to ground. If the connection to earth isn’t good enough or no lightning protection is integrated within the hydrostatic level sensor, then the electronics will take the entire amount of energy of the voltage pulse and fail.Which means protection is only as good as the earth grounding provided by the user.
In pressure gauge octa , where submersible pressure transmitters are generally used, WIKA provides an optionally integrated lightning protection in the level sensors. The sensor electronics will then be protected from local power surges and transient high voltage. Lightning protection is a mix of protection within the instrument and an excellent low impedance earth grounding.
Have เพรสเชอร์เกจ at the profiles of WIKAs submersible pressure transmitters LH-20 and LH-10.
Please use our contact form if you need further assistance.
Please find more info with this topic on our information platform ?Hydrostatic level measurement?